Classification
|
Terminal
|
Signal Function
|
Description
|
Signal Level
|
|
Sequence Input Signal
|
1
|
Forward run/stop
|
Forward run when closed, stop when open
|
Photo-coupler insulation
Input: +24 VDC 8mA
|
|
2
|
Reverse run/stop
|
Reverse run when closed, stop when open
|
|
3
|
External fault input
|
Fault when closed, normal state when open
|
Multi-function contact inputs (H1-01 to H1-06)
|
|
4
|
Fault reset input
|
Reset when closed
|
|
5
|
Master/Auxiliary change
(Multi-step speed reference 1)
|
Auxiliary frequency reference when closed
|
|
6
|
Multi-step speed reference 2
|
Effective when closed
|
|
7
|
Jog reference
|
Jog run when closed
|
|
8
|
External base block
|
Inv. Output stop when closed
|
|
11
|
Sequence control input common terminal
|
|
|
Analog input Signal
|
15
|
+15V Power supply output
|
For analog comm.and +15V power
supply
|
+15V
(Allowable current 20mA max.)
|
|
33
|
-15V Power supply output
|
For analog command –15V power
supply
|
-15V
(Allowable current 20mA max.)
|
|
13
|
Master frequency reference
|
-10 to +10V/-100% to + 100%
0
to+10V/100%
|
-10 to +10V (20kΩ), 0
to +10V/ (20kΩ)
|
|
14
|
4 to 20mA/100%
|
4 to 20mA (250Ω)
|
|
16
|
Multi-function analog input
|
-10 to +10V/ -100% to +100%
0 to+10V/100%
|
Auxiliary analog input (H3-05)
|
-10 to +10V (20kΩ), 0
to +10V/ (20kΩ)
|
|
17
|
Common terminal for control
circuit
|
0V
|
|
|
12
|
Connection to shield sheath
of signal lead
|
|
|
|
Sequence Output Signal
|
9
|
During running
(NO contact)
|
Closed when running
|
Multi-function
Contact output
|
Dry contact
Contact capacity:
250 VAC 1A or less
30VDC 1A or less
|
|
10
|
|
25
|
Zero speed detection
|
Makes at min. freq. (EI-09)
or less
|
Open collector output 48V 50
mA or less
|
|
26
|
Speed agree detection
|
Makes when the freq. Reaches
to ±1Hz of set freq.
|
|
27
|
Open collector output common
|
|
|
|
18
|
Fault contact output
(NO/NC contact)
|
Fault when closed between terminals
18 and 20
Fault when open between terminals
19 and 20
|
Dry contact
Contact capacity:
250 VAC 1A or less
30 VDC 1A or less
|
|
19
|
|
20
|
|
Analog output Signal
|
21
|
Frequency meter output
|
0 to + 10V/100% freq.
|
Multi-function
Analog monitor 1
(H4-01, H4-02)
|
0 to ± 10V Max. ± 5%
2 mA or less
|
|
22
|
Common
|
|
23
|
Current monitor
|
5 V / inverter rated current
|
Multi-function
Analog monitor 2
(H4-04,H4-05)
|