Drive Status Display
display 1 Drive standby
display 2 Drive accelerate
display 3 Drive speed agree
display 4 Drive decelerate

The drive will Trip when operating conditions outside it's specified limits are reached.
The EI-MINI has 6 protection functions.
display 5 OL. Motor current output greater than potentionmeter THRY setting, for a minimum time of 60 seconds.
display 6 OC. Instantaneous over current
display 7 OV. DC link over voltage (>=410 VDC)
display 8

UV. DC link under voltage (<=180 VDC)

display 9 OH. Drive Temperature Low and High (<= -5ºC or 23ºF) (>=80ºC or 176ºF)

Under these conditions, the drive will Trip and will display as error number and flash. If the fault condition persists, DC Link voltage or Drive temperature is too low or too high, then the drive cannot be Reset. When the fault condition is cleared, the drive may be Reset.

Power Connections

Remark: Rage G & F Models are all Three-phase input basic on (R.S.T) design.